5578-E
Heating and district heating controller
USAGE
- Building automation
APPLICATION
- Meter data recording
- Heating control
- Domestic hot water
- District heating
- Local heat supply
- Cooling control
- Solar thermal systems
- Temperature control
Special features
- Heating and district heating controller
- SAM DIGITAL READY
- Control of a primary heat exchanger or boiler with max. two mixing and one non-mixing heating circuit (both outdoor temperature controlled) as well as control of DHW heating in the secondary circuit
- Outdoor-temperature-controlled buffer storage tank control with max. two mixing heating circuits and continuous-flow hot water module
- Control of two outdoor-temperature-controlled heating circuits and a DHW heating with three valves in the primary circuit
- Control of three outdoor-temperature-controlled heating circuits with three valves in the primary circuit
- Extension to 6 control circuits with expansion module TROVIS I/O
- Direct access to the operating modes and essential parameters of the individual control circuits using a rotary pushbutton
- Enter and retrieve data intuitively by turning and pressing the button
- LC display with plain-text and icons
- 365-day clock with max. four time schedules (without TROVIS I/O) and automatic summer time/winter time changeover
- Max. three times-of-use per day (entered in steps of 15 minutes)
- Room panels can be connected for the individual heating circuits
- Demand-driven control by set point demand by subsequent controllers using device bus or an 0 to 10 V signal
- Applications including solar thermal DHW available
- Instantaneous heating systems with water flow sensor configurable
- Heating characteristic optionally based on gradient or four points
- Flexible limitation of the return flow temperature
- Adaptation: automatic adaptation of the heating characteristic (room temperature sensor required)
- Optimization: calculation of the best possible activation and deactivation times for heating (room temperature sensor required)
- Drying of jointless floors function with adjustable parameters
- Controller flash EPROM (operating system) can be updated
- Integrated meter bus interface for communication with max. three meter bus units
- Galvanically isolated RS-485 interface for Modbus RTU/device bus communication
- Ethernet interface for Modbus TCP/IP communication and connection to SAM DISTRICT ENERGY
- Configuration and parameter setting with TROVIS-VIEW Software over Ethernet interface
- Trend viewer
- Alarm table
- Time-stamped setting changes
- Event list
- Firmware installation guide: iOS / Android
Accessories
- Type 5227-4 Sensor for outdoor temperature
- Type 5277 und Type 5267-3 (contact sensor) Sensors for flow, return flow and storage tank temperature
- Type 5257-11 Sensor for room temperature
- Type 5257-51 Room Panel with potentiometer and mode selector switch
- TROVIS-VIEW software (free of charge)
- Surge arrester SA5000 for two-wire bus network
- TROVIS I/O expansion module
- SAM MOBILE Gateway for connection to SAM DISTRICT ENERGY
Options
- - - -
Information
Support
Software
-
Boot Manager
Tool zur Installation von Firmware-Updates
Tool for installing firmware updatesVersion 1.62[ZIP] -
Wichtige Hinweise zur Aktualisierung der Firmware auf Ihrem Gerät
Important information on updating the firmware on your device
[PDF] -
Erweiterungsmodul/Expansion module TROVIS I/O
Firmware V1.2.0SAM Gateway Konfigurator als Tool zur Installation von Firmware-Updates notwendig[ZIP]
SAM Gateway Configurator required as tool for installing firmware updates -
SAM Gateway Configurator
Tool zur Installation von Firmware-Updates
Tool for installing firmware updatesVersion 2.4.2[ZIP] -
Firmware V 3.05.xx
[B55]
Certificates
Only up-to-date documents are shown in the product selector. Check the documentation site for a list of all documents available.
Show all documents for Type 5578-E
Pin product
Pin items on your list and contact us if you have any product-related questions.
Back to product selector